Permit: TC-MDP-1023-01683

Parcel: 140442600


Addresses:

6203 E CAMPOLINA TR

Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/29/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready 9.29.25
Not ready
Work still being done
09/30/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.30.25
Missing staples at t ply bottom floor near top of sheet
RSP4s missing at s side.
Strap to beam missing s side
Nails over penetrating at plywood
A34 missing at ladder blocking per 47-SD5
10/02/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10/2/25: Staples at shear walls must not over penetrate sheathing and shall be no closer than 3/8" from edge. Staples must be spaced 3" o.c at all thermo-ply shearwalls. Anchor bolt spacing at shear walls must be 22" o.c, 16dx2 1/2" nails must be used at HTT4. stud at first floor garage wall must be properly secured at shearwall
10/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 10.3.25
Corrections made
APPROVED