Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Not Ready | 9.29.25 Not ready Work still being done |
|
| 09/30/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 9.30.25 Missing staples at t ply bottom floor near top of sheet RSP4s missing at s side. Strap to beam missing s side Nails over penetrating at plywood A34 missing at ladder blocking per 47-SD5 |
|
| 10/02/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 10/2/25: Staples at shear walls must not over penetrate sheathing and shall be no closer than 3/8" from edge. Staples must be spaced 3" o.c at all thermo-ply shearwalls. Anchor bolt spacing at shear walls must be 22" o.c, 16dx2 1/2" nails must be used at HTT4. stud at first floor garage wall must be properly secured at shearwall | |
| 10/03/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 10.3.25 Corrections made APPROVED |