Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
11/20/23: A35 clips missing at girder truss per section E on plans, shot pins pissing at closet in 2 bedroom unit, shot pins missing throughout 2 unit apartment, firewall nailing schedule not per plan, fascia on west side missing nails, exterior sheathing nail schedule not per plan, H25 clips missing throughout. |
| 11/22/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
11/22/23: contractor has corrected items from the 11/20/23 inspection. Okay to insulate and drywall interior walls. |