Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
11/24/23: 3 consecutive masa clips with one leg up (anchor bolts must be added to suffice hold down)throughout , anchor bolts missing 12" from edge of bottom plate, nail schedule at shear wall 11 not per plan, anchor bolt spacing at shear wall 11 not per plan, missing 3"x3" metal washer at shear wall 11, nailing at shear wall 9 not per schedule at bedroom, shear wall 9 at bedroom missing anchor bolt, |
| 11/29/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
11/29/23: All items from the 11/24/23 have been corrected. Okay to proceed with exterior dry-in of walls and roof. |