Permit: TC-MDP-0925-00592

Parcel: 141460830


Addresses:

9502 E FRIEDEL DR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/21/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9-21-26 shop pins are required at marked locations* coil strap missing per detail SD-2.52 at back window * missing nails at sheer wall upstairs south east corner* missing nails at Jo2 south east corner *missing hanger in primary bedroom at J01* missing nails at shear wall located west wall. Truss calcs and roof nailing walked OK and passed. Reinspection required