Permit: TC-MDP-0925-00554

Parcel: 132131710


Addresses:

2739 S AYALA ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
04/22/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required Provide a minimum of 18” at stand pipe for washer. Wiring incomplete at marked areas. Provide staples to secure electrical lines at marked areas. Provide nail plates at marked areas. Exhaust fans both wiring incomplete. Hall bath exhaust not connected. Provide a 10’ space between fresh air intake and any vent line. Seal all through penetrations to garage. (West wall) plans state per note 28 supply ducts in attic shall be insulated to a minimum of R8. R6 that is in place will not be within the thermal envelope. 4/22/2026
04/27/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed All corrections were made. 4/27/2026