Permit: TC-MDP-0925-00524

Parcel: 141156850

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
05/14/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Anchor bolts with washer plates missing from sw11 cannot be subbed for masa clips. Space at 23 0c

Anchor bolts at sw13 require washerplates and spacing of 17oc

Over penetration at sheathing interior shear and exterior
05/18/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed