Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2026 | COT - RSBU - Preslab | Re-inspection required | 7-8-2026 Reinforcement shall extend 2’ on each side of hold down. Pad must be properly compacted. PT cable shall not be exposed no more than 12” on stationary end & no more than 1” on pull end. End caps missing at stationary end. Footing shall be 12” in width as well as12” in height. All plumbing shall be wrapped at slab. Damaged sheathing at PT cable must be protected. Re-inspection is required. |
|
| 07/09/2026 | COT - RSBU - Preslab | Passed |