Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/04/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.4.2025
Front entry add flat blocks for shear wall, add another 2x4 under beam near stairs landing as marked, add web stiffener at marked locations to fill gap, missing 4ft wide exterior shear wall at landing area as marked, add 30 nails at top plate splices both sides at marked locations (NW corner area), staples over-penetrated second floor of south shear wall - check all staples, repair roof truss in north side of second floor H07 & CJ01.
09/08/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 9-8-25: partial pass replace kitchen shear wall due to too many over penetrations-structural integrity has been compromised. Shear wall to be checked at intermediates-okay to continue with construction at progress areas.
09/09/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 9.9.25
Corrections made