Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
05/19/2025 COT - RSBU - Roof Nailing  Re-inspection required 5/16/25
Not ready

5/19/25
1. Garage header is missing 1 king stud on each end.
2. Studs are broken at stairs, see marking in red.
3. Fire blocking needed at stringers, see stinger details.
05/22/2025 COT - RSBU - Roof Nailing  Re-inspection required Anchor bolts missing throughout exterior, anchor bolts at shear walls marked note c can be 1'4"oc and require 3x3" washer plates
05/29/2025 COT - RSBU - Roof Nailing  Re-inspection required 5-29-25: loose roof panel north side of loft above closet area
05/30/2025 COT - RSBU - Roof Nailing  Passed 5-30-25, approved. Okay to dry-in roof.