Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
07/10/2026 COT - RSPL - Plumbing Final  Re-inspection required 7/10/26: clean cap at driveway must be properly secured and proper clean out cover required at driveway, No gas meter installed at time of final, PRV requires No more than 6" Above finish grade, weep screed shall not terminate closer than 4" above finish grade, properly anchor clamps at ac electrical whip, GFCI AT KITCHEN COUNTER IMPROPERLY WIRED, Water hammer arrestor label shall be cleaned and legible, Thermostat height shall be no higher than 48" AFF, Dryer vent length required at dryer box, bracket at water heater must be properly installed. Properly secure bracket B-vent at air handler, threshold at garage shall be ADA compliant.
07/14/2026 COT - RSPL - Plumbing Final  Passed 07/14/2026
Corrections made.