Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
12/11/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 12-11-24, add nails to shear wall at owners suite, missing anchor bolts throughout-areas marked, add shot pin to marked location near laundry room, loose roof panel by bedroom 4 (marked it on the slab). STOPPED INSPECTION-ADDITIONAL ITEMS MSY BE NOTED.
12/16/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 12-16-24, missing bracing on truss H10A on W7& on each side of W8. Nail down all h-25's on interior load bearing walls by intermediate inspection. Also,Unable to check roof nailing. Roof is partially loaded with several rolls of tar paper and a pellet of materials over garage area. Therefore, submit a letter to the city stating roof nailing meets code requirements/ nailed per approved plans or remove items and reschedule an inspection. If you opt for the letter then it shall be submitted as an attachment to the city for review/approval. It must be approved prior to issuing a C of O.
12/18/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 12/18/24 bracing at truss H10A have been made. either a letter accepting responsibility for the roof must be submitted, stamped, and approved before final or tar paper along with other materials on roof must be taken off for re inspection off roof nailing.