Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Interior shear wall not per nailing schedule, missing studs to support girder truss at family room first floor, second floor missing h2.5 clips at truss. |
| 11/22/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|