Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
12/12/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready 12/12/23: all four of the interior shear walls are missing 1/2” wedge anchors @ 32”, one shear wall is not blocked, east exterior shear wall has misplaced hold-down and requires a engineered substitute. 3-ply girder is not correctly posted at all bearing points. INSPECTION STOPPED. MORE ITEM MAY BE ADDED AT NEXT INSPECTION. it is evident that this house was not QC walked before it was scheduled for a COT inspection. This seems to be the norm, rather than the exception.
12/15/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 12/15/23: missing anchor bolts at owner suite shear wall ok to continue to intermediates will check for anchor bolts then