Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
10/23/20: lateral bracing missing on T17 (mechanical trusses), Anchor bolts at shear walls require 3"x3" metal washer, anchor bolt spacing on east side of wall exceeds 12' (max spacing 6'), mass clips require minimum 7 nails to be properly installed (at entry masa installed with only 6 nails, anchor bolt spacing at shear wall 6 is 32" o.c, . |
| 10/26/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|