Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
11/26/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 11-26-25: The upstairs southeast bedroom has a 4' section of drywall installed 2" aff and this in itself does not meet code because screws/nails must be installed no closer than 3/8" from edges. Make corrections and reschedule drywall inspection.
12/01/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 12-1-25: screws at the southeast bedroom must be secured by manufactured specifications. Screws must be installed 3/8" from edge and 3/4" maximum. Screws in this case are installed to the framing members above 1" and screws are required at the edge from the measurements provided.
CORRECTION- SCREWS ARE REQUIRED AT 1/2” & 5/8” MAXIMUM.
12/02/2025 COT - RSBU - Interior Shear Bracing  Passed 12-2-25: interior shear bracing approved-okay to tape & texture.