Permit: TC-MDP-0724-00847

Parcel: 137322830


Addresses:

5563 S SWIRES RD

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/24/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9-24-24: missing bathroom/shower reinforcement, shot pins must be installed within 6" at the end of each plate & spaced at 24" o.c., add anchor bolts where installed closer than in the middle third of sill plate-tighten all anchor bolts, exterior nailing at sheathing not per plans-add nails add joints/edges. Nails can be no close than 3/8" from edges/joints and cannot over penetrate more than 1/16", missing H-25's at ledger-see detail H, Nail H-25 at entryway, add nails throughout roof decking-checking spacing and add nails where overpenetrated.
09/26/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 9-26-25: exterior clips/sheathing & framing approved. Okay to continue with construction.