Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0724-00820

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/04/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 10/4/24: Anchor bolts required throughout exterior perimeter wall and interior shear walls (spacing is greater than 23" o.c at shear walls 11 and 3x3 plates required) (spacing of anchor bolts greater than 6' o.c) (anchor bolts required 12" from edge of sill plate) (sill plates larger than 12" require 2 anchor bolts), garage opening requires 3king studs, shear wall fasteners not per schedule. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
10/09/2024 COT - RSBU - Exterior Clips/Sheathing  Passed 10/9/24: Noted items above have been corrected. Okay to proceed with rough-in.