Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0724-00820
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | 10/4/24: Anchor bolts required throughout exterior perimeter wall and interior shear walls (spacing is greater than 23" o.c at shear walls 11 and 3x3 plates required) (spacing of anchor bolts greater than 6' o.c) (anchor bolts required 12" from edge of sill plate) (sill plates larger than 12" require 2 anchor bolts), garage opening requires 3king studs, shear wall fasteners not per schedule. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. | |
10/09/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | 10/9/24: Noted items above have been corrected. Okay to proceed with rough-in. |