Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 10/04/2024 |
COT - RSBU - Roof NailingĀ |
|
Re-inspection required |
10/4/24: Anchor bolts required throughout exterior perimeter wall and interior shear walls (spacing is greater than 23" o.c at shear walls 11 and 3x3 plates required) (spacing of anchor bolts greater than 6' o.c) (anchor bolts required 12" from edge of sill plate) (sill plates larger than 12" require 2 anchor bolts), garage opening requires 3king studs, shear wall fasteners not per schedule. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 10/09/2024 |
COT - RSBU - Roof NailingĀ |
|
Passed |
10/9/24: Noted items above have been corrected. Okay to proceed with rough-in. |