Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0724-00816

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/07/2025 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 12/31/24 LUS24's needed at 2x6 on covered back patio. Anchor bolts must be secured, have framer walk through and check.


01/07/25
1. All SW11 or greater shear wall require anchor bolts with .0229"x3"x3" plate washer.
2. Patio not built per plan; the east beam should be a 6"x8" and pocket into wall; plans also call for BC6 post caps SE and SW posts.
01/13/2025 COT - RSBU - Exterior Clips/Sheathing  Passed 1/13/25: All issues from other inspections have been resolved and corrected. Okay to proceed with other work.
12/27/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 12/27/24 Missing many RSP clips throughout, missing nails on masa clips, anchor bolts needed throughout. Shot pins needed inside, shear wall at north wall needs nails at bottom plate. Straps missing at back of house. Inspection stopped.