Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
COT - RSEL - Electrical Final  Re-inspection required 6-16-25: max circuit breaker for a/c condenser is 40 amps-replace replace 50 amp breaker at panel to a 40amp., lower thermostat to 48" o.c., missing fire rated tag on garage door, missing receptacle cover at furnace, provide plans to verify max circuit for furnace.
06/23/2025 COT - RSEL - Electrical Final  Passed Approved. Corrections were made. 6/23/2025