Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
9/12/23: missing nail schedule all around exterior of both unit 1 and unit 2, nailing must be 3/8 from edge on exterior sheathing throughout, anchor bolts must be tightened, anchor bolt missing 12" from edge of bottom plate in unit 1, power pins at 24" o.c at bottom plate at firewall, unit 2 anchor bolt spacing is greater than 48" o.c at north bedroom. Nailing schedule at fire wall not met. |
| 09/14/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Fire wall still not complete. |
| 09/15/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|