Inspection Status: Canceled

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
09/25/2026 COT - RSPL - Plumbing Final  Canceled 9/25/26: canceled by contractor.
10/06/2026 COT - RSPL - Plumbing Final  Re-inspection required 10/6/26: EV receptacle must be rated for EVSE use, AFCI required throughout at multiple circuits (Kitchen,laundry,fridge,garbage disposal), HVAC Equipment is currently over-amped (min 25Amp, max 35amp), properly cap gray water and clean outs at laundry closet, Garbage disposal receptacle required to be GFCI, properly terminate HVAC condensate, All exterior plastic pipes must be protected from UV, properly support Condensate drain at roof with treated lumber. Insulation required at water heater.
10/12/2026 COT - RSPL - Plumbing Final  Passed 10/12/2026
All corrections made.