Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2026 | COT - RSME - Mechanical Final | Canceled | 9/25/26: canceled by contractor. | |
| 10/06/2026 | COT - RSME - Mechanical Final | Re-inspection required | 10/6/26: EV receptacle must be rated for EVSE use, AFCI required throughout at multiple circuits (Kitchen,laundry,fridge,garbage disposal), HVAC Equipment is currently over-amped (min 25Amp, max 35amp), properly cap gray water and clean outs at laundry closet, Garbage disposal receptacle required to be GFCI, properly terminate HVAC condensate, All exterior plastic pipes must be protected from UV, properly support Condensate drain at roof with treated lumber. Insulation required at water heater. | |
| 10/12/2026 | COT - RSME - Mechanical Final | Passed | 10/12/2026 All corrections made. |