Permit: TC-MDP-0623-01165

Parcel: 129141270


Addresses:

914 E 38TH ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 12/12/23: seal all penetrations going through top plate throughout, 16 GAGE (0.054 IN.) AND 1.5 IN. WIDE METAL TIE FASTENED ACROSS AND TO THE PLATE AT EACH SIDE OF THE NOTCH WITH 8-10 NAILS EACH SIDE on notch greater than 50% in master bedroom. R-8 flex is required to be installed per plans on attic (various locations with R-6 flex), passage in attic for mechanical appliance does not meet code (M1305.1.2), seal opening in vapor barrier with refrigerant lines coming in from outside.
12/15/2023 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed