Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Preslab
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2025 | COT - RSBU - Preslab | Passed | 11.04.2025 Corrections made same day. Verified updated plans showing deleted bollard in garage. Okay for concrete placement. |
|
| 11/04/2025 | COT - RSBU - Preslab | Re-inspection required | 11.04.2025 Add sleeve to >12” overexposed cable at southwest corner of slab, same cable has exposed wired midway that needs sleeve, move exterior STHD8 an inch away from slab edge, tamp down loose soil interior pad, missing 16”x16”x20” embedded footing in garage for bollard. |