Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 12-11-25: missing nails on exterior sheathing at a few locations- plans call for 6" o.c. Along edges and 12" o.c. In the field, add shot pins within 6" at the ends of plate, add backing at bathtub-see plans for details, add an anchor bolt at marked location north wall, add nails to lose roof panels at marked areas, add gable end bracing at center-cannot exceed 25'. | |
| 12/12/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 12-12-25: add nails at exterior 6" o.c. Along edges/splices- sheathing above exterior entryway and at marked locations, remove or properly nail any nails that are not flush at exterior sheathing, add shot pins within 6" at the ends of each plate. | |
| 12/16/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 12/16/2025 All corrections made from prior 12/12/25 inspection. |