Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2024 |
COT - RSBU - Roof NailingĀ |
|
Re-inspection required |
Missing shear walls. One at 1st bedroom. 2nd at great room area. Shear wall nailing not per schedule. Add anchor bolts to breaks at bottom plates. Add cut nails or shot pins to all loose interior plates. Add fire blocking and secure wall at shower. Add h25 at truss above window great room area and 1st bedroom areas. Add double studs underneath girder truss. Loose roof sheathing at hips. 8/15/2024 |
| 08/19/2024 |
COT - RSBU - Roof NailingĀ |
|
Passed |
Corrections were made. 8/19/2024 |