Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
03/20/2025 COT - RSEL - Electrical Final  Re-inspection required 20 March 25
1. Thermostat is too high downstairs and sitting above counter space, per plan thermostat should be no higher than 48 inches.
2. GFCI will not reset in laundry room and washer machine outlet is not on GFCI protected circuit.
3. HVAC is on a 40 Amp breaker needs to be on a 50.
03/25/2025 COT - RSEL - Electrical Final  Passed 3/25/25 Corrections made