Inspection Status: Partial Pass
Inspection History: COT - RSEL - Grounding/Bonding
| Date |
Description |
Inspector |
Results |
Comments |
| 06/04/2025 |
COT - RSEL - Grounding/Bonding |
|
Partial Pass |
6-4-25: partial pass for ufer only. |
| 07/09/2025 |
COT - RSEL - Grounding/Bonding |
|
Re-inspection required |
7-9-25: firefoam penetration at garage, near east window directly in front of island, & bedroom top plates, seal penetrations at t-ply in bedrooms and throughout house-some marked, walk house and seal accordingly,receptacle spacing in middle eastern bedroom at 13 1/2'-max spacing is 12'. Either add another receptacle or adjust to 12' max., missing acorn clamp at ufer. |
| 07/11/2025 |
COT - RSEL - Grounding/Bonding |
|
Passed |
7-11-25: residential intermediate inspection approved. Okay to construction. |