Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
10/20/2025 RSBU - Building Final  Re-inspection required 10.20.2025
Circuit tripped all outlets in bathroom and primary bedroom when testing GFCI, as well as in great room near kitchen trips fan - plans show GFCI on separate circuits. Insulate exposed hot water line on water heater in garage. Mark which electric heat kit, if any, used on air handler label in attic area.
10/21/2025 RSBU - Building Final  Passed 10/21/25 corrections made