Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Interior Shear Bracing
| Date |
Description |
Inspector |
Results |
Comments |
| 07/07/2025 |
COT - RSBU - Interior Shear Bracing |
|
Re-inspection required |
7-7-25: screws shall be no closer than 3/8" from edges/joints and cannot penetrate more than 1/16". Add screws along base of drywall throughout and screws using listed above Information/details. |
| 07/08/2025 |
COT - RSBU - Interior Shear Bracing |
|
Re-inspection required |
7-8-25: missing screws at garage in several areas, overpenetrated screws throughput garage and at family room Per ASTM C840: fasteners must not break the face of drywall paper which mean screws/nails should be driven below the surface, but not more than 1/32 inch deep into the face of the drywall. The face paper must remain intact to maintain holding strength and prevent surface damage. |
| 07/09/2025 |
COT - RSBU - Interior Shear Bracing |
|
Passed |
7-9-25: okay for tape & texture. |