Permit: TC-MDP-0524-00565

Parcel: 140443840


Addresses:

6137 E FALCONRY TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
07/07/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 7-7-25: screws shall be no closer than 3/8" from edges/joints and cannot penetrate more than 1/16". Add screws along base of drywall throughout and screws using listed above Information/details.
07/08/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 7-8-25: missing screws at garage in several areas, overpenetrated screws throughput garage and at family room Per ASTM C840: fasteners must not break the face of drywall paper which mean screws/nails should be driven below the surface, but not more than 1/32 inch deep into the face of the drywall. The face paper must remain intact to maintain holding strength and prevent surface damage.
07/09/2025 COT - RSBU - Interior Shear Bracing  Passed 7-9-25: okay for tape & texture.