Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/16/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.16.2025
Staples at shear wall throughout needs to be flush - see red markings. HTT4 or 5 not set in place at interior shear walls, add anchor bolts 12" from edge of sole throughout, shear wall at south side requires anchor bolts or masa clips not per schedule, replace section of garage shear wall as marked. Next inspector needs to do full first & second floor walkthrough. STOPPED INSPECTION, MORE ITEMS COULD BE PRESENT.
09/17/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 9.17.2025
Partial pending placement of HTT4s downstairs on T-ply walls. Gable end roof trusses notched in or modified in the field require engineering letter and specifications from truss manufacturer. Corrections made to yesterday's inspection.
09/26/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 9/26/25
1. Need engineer letter for notching gable end trusses.
09/30/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed