Permit: TC-MDP-0524-00556

Parcel: 140443780


Addresses:

6089 E FALCONRY TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
08/29/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Add studs underneath GT at garage and entry. Add stud underneath GLB. H25's need to be clipped to load bearing top plates in garage. Add anchor bolts at garage walls. Add washers and nuts. Add anchor bolts due to excessive masa legs up. Add stud in kitchen area. Missing gable end trusses. North end. Nailing at perimeter and interior walls not per schedule. Add staples to therm ply at garage. 8/29/2024
08/30/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Add studs underneath GT at garage and entry. Add stud underneath GLB. H25's need to be clipped to load bearing top plates in garage. Add anchor bolts at garage walls. Add washers and nuts. Add anchor bolts due to excessive masa legs up. Add stud in kitchen area. Missing gable end trusses. North end. Nailing at perimeter and interior walls not per schedule. Add staples to therm ply at garage. 8/29/2024
8/30/24: Hilti XCP at interior shear wall shall be 7" o,c, add studs at kitchen wall,
09/04/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed Corrections were made. 9/4/2024