Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-0524-00556
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2024 | COT - RSBU - Roof Nailing | Re-inspection required | Add studs underneath GT at garage and entry. Add stud underneath GLB. H25's need to be clipped to load bearing top plates in garage. Add anchor bolts at garage walls. Add washers and nuts. Add anchor bolts due to excessive masa legs up. Add stud in kitchen area. Missing gable end trusses. North end. Nailing at perimeter and interior walls not per schedule. Add staples to therm ply at garage. 8/29/2024 | |
08/30/2024 | COT - RSBU - Roof Nailing | Re-inspection required | Add studs underneath GT at garage and entry. Add stud underneath GLB. H25's need to be clipped to load bearing top plates in garage. Add anchor bolts at garage walls. Add washers and nuts. Add anchor bolts due to excessive masa legs up. Add stud in kitchen area. Missing gable end trusses. North end. Nailing at perimeter and interior walls not per schedule. Add staples to therm ply at garage. 8/29/2024 8/30/24: Hilti XCP at interior shear wall shall be 7" o,c, add studs at kitchen wall, |
|
09/04/2024 | COT - RSBU - Roof Nailing | Passed | Corrections were made. 9/4/2024 |