Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Interior Shear BracingĀ
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2026 | COT - RSBU - Interior Shear BracingĀ | Re-inspection required | 7/1/26: fasteners cannot be closer than 3/8" from edge and shall penetrate no more than 1/8" from edge. Throughout the entire house. (All areas were not walked) please have sub-contractors walk the entire house | |
| 07/02/2026 | COT - RSBU - Interior Shear BracingĀ | Passed | 07/02/2026 Corrections made to drywall screw spacing. |