Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
10/22/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10/22/26: missing 2 STHD10 at garage & exterior wall, SW13-over penetrated nails (cannot exceed 1/16" & cannot be closer than 3/8" from joints/edges)-add nails according to schedule, missing edge nailing at belly board throughout, missing sheathing at exterior wall at northwest corner, add anchor bolt to marked exterior wall at northwest corner-any plate 12" in length requires a minimum of 2 anchors, add a shot pin to marked area, missing nails at top plate splices, check all shear walls and add nails-not all areas marked but I noted over penetrations, too close to edges, and spacing not per schedules. Stopped inspection-additional items may be noted. Note: 1st floor not entirely walked & 2nd floor not walked at all.
10/27/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 10/27/2026
Corrections made. Walked second floor and verified added sister stud to damaged stud at rear west wall as marked. Added fasteners to loose roof panels.