Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/23/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 7-23-25: missing A34 at gable end truss bracing at garage-see detail S5.2-5,missing gable end bracing with A34 west of garage, RSP4's on west side and and RSP4 on north side, missing nails at exterior sheathing-north side, add anchor bolt to marked location at north bedroom shear wall, add shot pins marked locations.
07/24/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 7.24.25
Satisfactory corrections verified on site.