Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Gas Pressure Test
| Date |
Description |
Inspector |
Results |
Comments |
| 10/28/2024 |
COT - RSPL - Gas Pressure Test |
|
Re-inspection required |
10-28-24, pressurize gas to 15 psi(gage at 9psi), properly seal vapor barrier at staircase, upstairs bedrooms. Master bedroom missing an approximate 16' by 5' section of barrier, missing fire foam at upstairs bath 2, fire foam upstairs chute, remove debris from truss at garage and upstairs northeast bedroom, install larger fha plate at garage to properly protect copper line near pex on east wall. Stopped inspection, additional items needing correction may be noted. |
| 10/29/2024 |
COT - RSPL - Gas Pressure Test |
|
Re-inspection required |
10-29-24, gas pressure test not approved. Test shall be at 15 psi for minimum of 10 minutes. Gage set at 11 psi. |
| 10/31/2024 |
COT - RSPL - Gas Pressure Test |
|
Passed |
10-31-24, previously noted items have been corrected. Gas pressure test verified at 15 psi. Okay to proceed with construction. |