Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Progress
Permit Number - TC-MDP-0424-00395
Inspection Description - RSBU - Building Progress
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2024 | RSBU - Building Progress | Re-inspection required | 10-28-24, Gas pressure must be at 15 psi, seal,all penetrations to vapor barrier at staircase, fire foam upstairs loft decking, fire foam missing at master bedroom double top plate east wall,section of vapor barrier missing in bedroom 3. Inspection stopped-additional items requiring correction may be noted. | |
10/29/2024 | RSBU - Building Progress | Re-inspection required | 10-29-24, missing fire foam from downstairs to upstairs decking at loft, DWV not under test upstairs shower. | |
10/31/2024 | RSBU - Building Progress | Partial Pass | 10-31-24, (partial pass) provide photos of sealed vapor barrier prior to lath for northeast bedroom. Okay to proceed with construction. |