Permit: TC-MDP-0326-00168

Parcel: 141461880


Addresses:

9593 E WYNALDA DR

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
09/04/2026 COT - RSEL - Electrical Final  Re-inspection required 8.4.26
1. Missing k.o. Seal at the bottom of service panel.
2. Paint all exterior plastics
3. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed.
4. HVAC condenser needs to be on GFCI breaker.
5. Dryer must be GFCI protected
6. EV receptacle must be GFCI protected
7. Install proper EV receptacle
8. Microwave must be GFCI protected
09/09/2026 COT - RSEL - Electrical Final  Re-inspection required 9-9-26 2. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed. *HVAC condenser needs to be on GFCI breaker. *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected
09/10/2026 COT - RSEL - Electrical Final  Re-inspection required 9-10-26 Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed *HVAC condenser needs to be on GFCI breaker *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected * GFCI breaker required for range as well
09/11/2026 COT - RSEL - Electrical Final  Passed 9-11-26 all corrections have been made. Also blanks are installed at kitchen island for future pop-up power