Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-MDP-0326-00168

Parcel: 141461880


Addresses:

9593 E WYNALDA DR

Inspection Status: Not Ready

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
07/07/2026 RSBU - Building Final  Not Ready 7-7-2026 please revise panel schedule additional two circuits and panel. Called out during electrical clearance
09/04/2026 RSBU - Building Final  Re-inspection required 8.4.26
1. Missing k.o. Seal at the bottom of service panel.
2. Paint all exterior plastics
3. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed.
4. HVAC condenser needs to be on GFCI breaker.
5. Dryer must be GFCI protected
6. EV receptacle must be GFCI protected
7. Install proper EV receptacle
8. Microwave must be GFCI protected
09/09/2026 RSBU - Building Final  Re-inspection required 9-9-26 2. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed. *HVAC condenser needs to be on GFCI breaker. *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected
09/10/2026 RSBU - Building Final  Re-inspection required 9-10-26 Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed *HVAC condenser needs to be on GFCI breaker *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected * GFCI breaker required for range as well
09/11/2026 RSBU - Building Final  Partial Pass 9-11-26 all previous items have been corrected kitchen island receptacles were blank for future pop-up receptacle use. partial pass, pending unsatisfied conditions.