Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2026 | RSBU - Building Final | Not Ready | 7-7-2026 please revise panel schedule additional two circuits and panel. Called out during electrical clearance | |
| 09/04/2026 | RSBU - Building Final | Re-inspection required | 8.4.26 1. Missing k.o. Seal at the bottom of service panel. 2. Paint all exterior plastics 3. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed. 4. HVAC condenser needs to be on GFCI breaker. 5. Dryer must be GFCI protected 6. EV receptacle must be GFCI protected 7. Install proper EV receptacle 8. Microwave must be GFCI protected |
|
| 09/09/2026 | RSBU - Building Final | Re-inspection required | 9-9-26 2. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed. *HVAC condenser needs to be on GFCI breaker. *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected | |
| 09/10/2026 | RSBU - Building Final | Re-inspection required | 9-10-26 Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed *HVAC condenser needs to be on GFCI breaker *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected * GFCI breaker required for range as well | |
| 09/11/2026 | RSBU - Building Final | Partial Pass | 9-11-26 all previous items have been corrected kitchen island receptacles were blank for future pop-up receptacle use. partial pass, pending unsatisfied conditions. |