Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2026 | COT - RSME - Mechanical Final | Re-inspection required | 8.4.26 1. Missing k.o. Seal at the bottom of service panel. 2. Paint all exterior plastics 3. Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed. 4. HVAC condenser needs to be on GFCI breaker. 5. Dryer must be GFCI protected 6. EV receptacle must be GFCI protected 7. Install proper EV receptacle 8. Microwave must be GFCI protected |
|
| 09/09/2026 | COT - RSME - Mechanical Final | Re-inspection required | 9-9-26 Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed *HVAC condenser needs to be on GFCI breaker *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected | |
| 09/10/2026 | COT - RSME - Mechanical Final | Re-inspection required | 9-10-26 Kitchen island cannot have receptacles on the sides only. Pop up surface mounts are allowed *HVAC condenser needs to be on GFCI breaker *Dryer must be GFCI protected *EV receptacle must be GFCI protected *Install proper EV receptacle *Microwave must be GFCI protected * GFCI breaker required for range as well | |
| 09/11/2026 | COT - RSME - Mechanical Final | Passed | 9-11-26 all corrections have been made. Also blanks are installed at kitchen island for future pop-up power |