Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Gas Pressure Test
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2026 | COT - RSPL - Gas Pressure Test | Re-inspection required | 6/30/26: Nail plates required where plumbing/electrical come within 1 1/4" throughout, properly secure exhaust vent 1st floor, repair torn flex at 1st floor near stair, please recall. Properly support flex every 4' throughout. | |
| 07/06/2026 | COT - RSPL - Gas Pressure Test | Canceled | 7.6.26 Canceled |
|
| 07/07/2026 | COT - RSPL - Gas Pressure Test | Not Applicable |