Permit: TC-MDP-0326-00154

Parcel: 141461950


Addresses:

9649 E WYNALDA DR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
05/08/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 05/08/2026
Add studs on south wall continuous to foundation for girder truss as marked, add anchor bolt on south wall as marked where Masa clip has one arm up near plate edge, add steel 3" washer plates to SW11 per note L in shear wall schedule sheet S2.1, rear ratio calls for use of hangers instead of pocket beam cutting through shear wall, add 2x4 stiffener to diagonal end bracing exceed 6’ per detail 306 upstairs.
05/11/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass Partial pass pending revision or correction for pocket beam at shear
05/13/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 5.13.26
Approved - corrections made