Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 02/17/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
2-17-26: missing backing at restrooms-see plans for installation requirements, add shot pins within 6" at the end of plate and a minimum of 2 shot pins are required per plate. Add stud shoe at marked location-over notched more than 40% at non bearing wall, add nails to exterior sheathing at marked locations. Reschedule unable to thoroughly inspect southeast unit due to workers installing MEP's. |
| 02/18/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
2-18-26: exterior clips/sheathing approved. |