Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
10/04/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10-4-24, missing lateral bracing-see truss calculations for details. Also, several areas on roof require additional nailing, add shot pins throughout interior framing, missing/loose anchor bolts. Exterior clip requires additional nailing-areas in question marked
10/07/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Several areas require additional nailing
10/7/24: shot pins required 24" o.c at interior walls, damaged sill plates must be replaced, shot pins required 6" from edge of sill plate, exterior sheathing must be properly fastened (fasteners shall be 3/8" from edge and not penetrate more than 1/8".
10/09/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed