Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Interior Shear Bracing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2025 | COT - RSBU - Interior Shear Bracing | Passed | ||
| 10/04/2024 | COT - RSBU - Interior Shear Bracing | Not Ready | ||
| 10/07/2024 | COT - RSBU - Interior Shear Bracing | Re-inspection required | Several areas require additional nailing 10/7/24: shot pins required 24" o.c at interior walls, damaged sill plates must be replaced, shot pins required 6" from edge of sill plate, exterior sheathing must be properly fastened (fasteners shall be 3/8" from edge and not penetrate more than 1/8". |
|
| 10/09/2024 | COT - RSBU - Interior Shear Bracing | Re-inspection required | Several areas require additional nailing 10/7/24: shot pins required 24" o.c at interior walls, damaged sill plates must be replaced, shot pins required 6" from edge of sill plate, exterior sheathing must be properly fastened (fasteners shall be 3/8" from edge and not penetrate more than 1/8". 10/9/24: this is inspection is for drywall nailing. |
|
| 10/15/2024 | COT - RSBU - Interior Shear Bracing | Partial Pass | Several areas require additional nailing 10/7/24: shot pins required 24" o.c at interior walls, damaged sill plates must be replaced, shot pins required 6" from edge of sill plate, exterior sheathing must be properly fastened (fasteners shall be 3/8" from edge and not penetrate more than 1/8". 10/9/24: this is inspection is for drywall nailing. 10-15-24, listed items from 10-7-24 have been corrected. |