Permit: TC-MDP-0324-00303

Parcel: 140443470


Addresses:

6200 E CAMPOLINA TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
09/19/2025 COT - RSBU - Roof Nailing  Re-inspection required 9.19.2025
Masa clip needs nails on SW corner area. Anchor bolt at back porch as marked, add nails on south shear wall as marked, add anchors for missing masa clips on garage Tply wall 22" on center. Back T-ply shear wall calls for 7ft wide wall - only 4ft measured, add pressure clip 8ft on center, SD4-36 detail requires ladder blocking using 2x6’s instead of 2x4’s. Detail SD4-31 requires 2x4 flat brace since length is greater than 6ft. Add roof nails in bedroom north of great room. Columns require anchor bolts since masa clips has both arms raised. A04M trusses missing behind garage - this requires revised truss calc plan.
09/22/2025 COT - RSBU - Roof Nailing  Partial Pass 9/22/25
Still missing A04M truss calcs revisions
09/25/2025 COT - RSBU - Roof Nailing  Re-inspection required
10/14/2025 COT - RSBU - Roof Nailing  Passed 10/14/25
Pass