Permit: TC-MDP-0226-00059

Parcel: 140442560


Addresses:

6219 E CAMPOLINA TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
07/06/2026 COT - RSBU - Interior Shear Bracing  Re-inspection required 7-6-2026 fasteners need to be no less then 3/8" from edge [throughout] fastener should not penetrate drywall more than eighth of an inch (1/8") also fasteners should be placed at 12 inches on center throughout. Please re-walk before calling it in. Wires at garage Entry are nicked, will need to fix. Second floor was not walked.
07/07/2026 COT - RSBU - Interior Shear Bracing  Partial Pass 7.7.26
1. Damaged fire rated ceiling drywall just above garage door.
2. Drywall screws used for various light/fan bracket upstairs.
07/09/2026 COT - RSBU - Interior Shear Bracing  Re-inspection required (with fee) 7-9-2026 house has been taped and mud prior to inspection approval, please remove tape from joints to verify proper fastener spacing from edge will also require magnents for spacing for fasteners throughout.
07/10/2026 COT - RSBU - Interior Shear Bracing  Re-inspection required Damaged fire rated ceiling drywall just above garage door.