Parcel: 140443630


Addresses:

6054 E FALCONRY TR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0224-00228

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/29/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 4/29/24: T-ply at shear walls not fastened per schedule, Anchor bolts missing 12" from sill plate edge, more than 3 continuous M.A.S.A clips with one leg up throughout (add anchor bolts to meet proper requirements), holdown at garage on north east corner not per plans (plans call for HTT5-KT/HTT45-KT).
04/30/2024 COT - RSBU - Exterior Clips/Sheathing  Passed